ELET 285: Process Control & Instrumentation

An applied laboratory curriculum exploring industrial relay logic, electromechanical actuators, timers, level and flow dynamics, and the critical engineering transition from open-loop timed sequence control to closed-loop sensor-regulated feedback systems.

Interactive Simulation Laboratories

Select a laboratory below to launch the drag-and-drop relay logic matrix, animate tank hydraulics, and test industrial control strategies:

Laboratory 1

Open-Loop Tank Level Control via Relay Timer

Investigate timed sequence process control without feedback. Construct a 3-wire Start/Stop seal-in latch and an On-Delay Timer (TON) circuit to meter fluid into a 10-gallon tank. Test the system under nominal conditions, unmetered downstream leaks, and residual starting volumes.

  • Control Strategy: Timed fill sequence ($t = \text{Target Volume} / Q$)
  • Relay Instructions: N.O. Pushbuttons, N.C. Pushbuttons, Relays (CR1), On-Delay Timers (T1:TON)
  • Lab Experiments: Calibration run, load disturbance underfill, and pre-fill overflow hazard

Laboratory 2

Closed-Loop Level Control via High-Level Switch (LSH-1)

Transition to true closed-loop negative feedback. Replace the blind timer with a discrete float switch (LSH-1) mounted at the 75% cutoff mark (7.5 Gallons). Verify how sensor feedback completely overcomes supply pressure surges and leaky drain valves.

  • Control Strategy: Sensor feedback cutoff & Tank Full panel indication
  • Field Devices: Float switch (LSH-1 at 75%), Pilot Lamp (PL-1), Solenoid Valve (SOL-1)
  • Lab Experiments: Nominal closed-loop cutoff, supply pressure disturbance, and leak rejection

Comparative Analysis: Open-Loop vs. Closed-Loop Level Control

Compare key operational and safety metrics between the two control schemes investigated across Lab 1 and Lab 2:

Metric / Parameter Lab 1: Open-Loop (Relay Timer) Lab 2: Closed-Loop (LSH-1 Switch)
Feedback Mechanism None (Operates blindly on time $t$) Direct process sensor (Float switch LSH-1 at 75%)
Fill Cutoff Trigger Timer reaches Preset value (T1_DN = 1) Liquid contacts sensor float (LSH1 = 1)
Supply Pressure Variation Fails: results in underfill or overflow Compensated: fill time adjusts; level is exact
Discharge Leak Disturbance Fails: level falls short proportional to leak Compensated: continues fill until level hits 7.5 Gal
Residual Starting Level ($V_0 > 0$) Hazardous: tank overflows and spills liquid Safe: shuts off immediately upon reaching 7.5 Gal
Instrumentation Cost Lower initial cost (No vessel penetrations) Requires level sensor mount, wiring, calibration
Typical Industrial Role Batch metering when fluid source is tightly regulated Critical level regulation, high-level spill prevention

Relay Ladder Logic Implementation Details

Compare the schematic structure of the open-loop timer circuit with the closed-loop level switch circuit:

Rung 000: 3-Wire Seal-In Control (Both Labs)

The momentary green Start button (PB1_START, N.O.) is wired in parallel with an auxiliary contact from control relay CR1. When Start is pressed, CR1 energizes and latches itself ON through the seal-in branch.

Fail-Safe Stop Button: Physical stop pushbuttons use Normally Closed (N.C.) contacts. In software ladder logic, a Normally Closed instruction (--[/]--) evaluates to True when unpressed, and opens when the button is hit, breaking the rung and dropping the latch.

Lab 1 vs. Lab 2 Output Interlocks

Lab 1 (Timer Cutoff): The solenoid valve SOL1_VALVE is energized through CR1 and a Normally Closed contact addressed to T1_DN. When the preset timer elapses, the contact opens, terminating flow regardless of liquid position.

Lab 2 (Sensor Cutoff): SOL1_VALVE is energized through CR1 and a Normally Closed contact addressed to LSH1. Power is cut only when fluid physically tilts the float. A parallel Normally Open contact triggers the PL1_FULL indicator lamp.